Our Feeder pillars are of compact design while using space saving fuse switch units such as Vertical Strip Fuse Units.
These units are designed for Outdoor type use with strong and robust construction. Feeder Pillars with GRP enclosures can also be supplied on request.
ENCLOSURE AND BUSBAR SYSTEM | 3 Phase, 4 Wire, 415V AC, 50 Hz system with Earthing |
CURRENT RATING | Upto 1600A |
SHORT CIRCUIT RATING | from 25kA upto 50kA rated for 1 Second |
DEGREE OF PROTECTION | IP54/ IP55 – INDOOR and OUTDOOR |
TYPE OF CONSTRUCTION | Form 2b Non – Compartmentalized – SINGLE DOOR/ DOUBLE DOOR |
MOUNTING | Free Standing, Floor mounted |
INCOMER DEVICE | Drawout/ Fixed – ACB/ MCCB |
OUTGOING DEVICES | Fixed – MCCB/ HRC Fuse units Vertical Strip Fuse way units |
ENCLOSURE MATERIAL | CRCA/ GI Sheet Steel as per applicable IS Standards |
BUSBAR MATERIAL | ETP Grade Tinned Copper OR EC Grade Aluminium as per applicable IS Standards |
POWDER COATING | Special Painting treatment and application to ensure Salt spray endurance of 1000 Hours. Customized painting process as per Customer request shall also be offered. |